Electrosoft IsoArc gloves provide insulation against electric shock up to 1000V with the added benefit of arc flash protection up to 21.6 calories/cm2

hsp-logo

Product Numbers

Details

2092002

ELECTROSOFT ISOARC CL0 36CM Flock Lined Grip Pattern
Latex insulating glove with Arc Rating of 21.6 cal/cm2. Class 0. Length : 36 cm. (Sizes 7 to 11)



Key Features

  • Electrical protection up to 1000V
  • Arc Flash protection up to 21.6 cal/cm2
  • Soft and thin - offer excellent dexterity
  • Grip finish on palm

Recommended Industries/Use

Hazards

Regulations

  • Standards EN 60 903-2003, CEI 903-2002

Historical Brand

Sofraf

Warranty Information

Honeywell warrants that it's Protective Gloves are free from defects in material and workmanship. This limited warranty does not cover any product or component found to have been altered, misused, abused, tampered with or improperly maintained or to have deteriorated due to aging of any component made of rubber or any other elastomer. The limited warranty does not cover any damage, loss or expense due to damage caused by accident, abuse, improper maintenence, use or misuse of the product.

Specification Information

Honeywell tests gloves in accordance with guidelines set by the European regulations (EN). To view testing information on individual part numbers, refer to the Technical Specification documents located in the Downloads and Documentation section.



Storage : Store in original packaging (Opaque and anti-UV packaging used for protection and instructions for use). Do not compact or fold. Do not expose to heat sources (sunlight, radiators, artificial light). Store between 10°C and 21°C.
Inspection : Before each use, carry out a visual inspection and check the glove inflation. Any puncture or perforation makes the gloves unusable.
Precautions : Do not expose to solvents or chemicals that may cause deterioration. Do not use the glove when damp.
Cleaning : use water and soap. Dry below 65°C with ambient humidity.

 

Minimum packaging : 1 pair. Opaque and antiUV single packaging used for protection and instructions for use. The Electrosoft gloves, made of latex, are free of allergies ( process to clean off proteine of latex). In case of allergic reaction to latex please do not use electrosft gloves.
Marking : The date of the electrical test made at the end of production is placed on every glove bag, as well as a lot number to ensure product traceability.Gloves that are used frequently should be tested at intervals less than 6 month. Gloves that are used only occasionally should be tested after each use and, in any case, at intervals of not more than 12 months. Gloves held in stock should be retested at intervals not exceeding 12 months.

Related Products

Honeywell Safety Products Australia / New Zealand

Honeywell Safety Products Australia Pty Ltd

43 Garden Boulevard,

Dingley, Victoria 3172

Australia Tel: 1300 139 166

Australia Fax: 1300 362 491
 

New Zealand Tel: 0800 322 200

New Zealand Fax: 0800 322 266
 

Data Sheet Lists

Click this icon to list the data sheets you'd like to download. Once submitted, the list will be saved for up to five days. You may list up to 20 items. Remember, lists that are not submitted will be lost when you either close your browser or log out of My Safety.